Wen 3500 Generator Section Locate the vented cover to the left of the Muffler and remove the two screws holding the cover in place. The screws are
Remove the Brush Assembly by loosening the 7mm screw. Check the carbon on the Brushes for any broken ends or excessive wear. The brushes are sprin
The Brushes make connection with the Rotor by riding on the Slip Rings. With the Brush Assembly removed you should clean the slip rings of carbon bu
Attach the wires from the Voltage Regulator to the Brush Assembly. Polarity is important. The Positive wire from the Voltage Regulator is marked wit
The Generator motor should NOT be running during these tests. Each set should make a closed circuit when tested with an Ohm meter. You should get a r
…and a quick-disconnect terminal on the other. As noted above, the Brush Assembly polarity is important. Make sure the Voltage Regulator wires goin
Position the Sealing Grommet before reinstalling the cover. Reattach Cover and tighten the 7mm screws.